D2.23 Signs on doors
-
A sign, to alert persons that the operation of certain doors must not be impaired, must be installed where it can readily be seen on, or adjacent to, a
-
-
required fire door providing direct access to a fire-isolated exit, except a door providing direct egress from a sole-occupancy unit in a Class 2 or 3 building or Class 4 part; and
-
required smoke door,
on the side of the door that faces a person seeking egress and, if the door is fitted with a device for holding it in the open position, on either the wall adjacent to the doorway or both sides of the door; and
-
-
-
fire door forming part of a horizontal exit; and
-
smoke door that swings in both directions; and
-
door leading from a fire isolated exit to a road or open space, on each side of the door.
-
-
-
A sign referred to in (a) must be in capital letters not less than 20 mm high in a colour contrasting with the background and state?
-
for an automatic door held open by an automatic hold-open device?
FIRE SAFETY DOOR DO NOT OBSTRUCT; or -
for a self-closing door;
FIRE SAFETY DOOR
DO NOT OBSTRUCT
DO NOT KEEP OPEN; or -
for a door discharging from a fire-isolated exit
FIRE SAFETY DOOR?DO NOT OBSTRUCT.
-
​
ALL SIGNS ARE SELF ADHESIVE (STICKERS)